Workers' Compensation Fundamentals
Workers' compensation is the mandatory insurance system that backs every licensed tradesman in the field. How it actually works, what protects you, and what costs you.
Counts for HVAC, Electrical, Plumbing
Every hour in our packages is sold on its own for $19. Same content, same 50 minute timer, same certificate, same DBPR reporting. Filter by your trade to see only the hours your board accepts.
23 hours
Workers' compensation is the mandatory insurance system that backs every licensed tradesman in the field. How it actually works, what protects you, and what costs you.
Counts for HVAC, Electrical, Plumbing
OSHA standards are the federal floor for workplace safety. The rules, the rights, and the hazards that put trade workers in the system.
Counts for HVAC, Electrical, Plumbing
Technical skill keeps the work in the truck running. Business skill keeps the business alive. The practices that decide whether you are profitable next year or out of business.
Counts for HVAC, Electrical, Plumbing
The laws and rules that govern Florida's Class A, B and C air conditioning, mechanical and plumbing contractors: F.S. Chapter 489 Part I, F.S. Chapter 455, and the CILB rules in F.A.C. 61G4.
Counts for HVAC, Plumbing
The 2026 Florida Building Code, Mechanical, 9th Edition takes effect December 31, 2026. It is built on the 2024 IMC, but Florida rewrites a long list of sections for hurricanes, flood zones and a hot, humid climate.
The 2024 IMC reorganizes the administrative chapter, adds definitions from the IBC and IFC, updates rooftop access, and lays the groundwork for the biggest refrigerant transition in decades.
The single largest change in the 2024 IMC: A2L refrigerants in human comfort air conditioning, driven by the EPA mandate to phase down HFCs 85 percent over 15 years. Chapter 11, rewritten.
Six documented changes in Chapter 4, including the largest single increase in dwelling unit ventilation rates in over a decade, plus new Table 403.3.1.1 rows for occupancies the old table never covered.
Nine documented changes in Chapter 5, the second densest change block in the edition: multifamily common exhaust, commercial dryers, range hoods in care facilities, grease duct testing and kitchen hood exceptions.
Chapter 6 governs duct construction, materials and installation. The 2024 edition changes closet return air, duct coverings and linings, and through penetrations with fire dampers, on top of the fundamentals every install gets inspected against.
The source standard behind most of IMC Table 403.3.1.1, ASHRAE 62.1, and the current practice around it: IAQ measurement, demand controlled ventilation, energy recovery and commissioning.
Chapter 10 governs boilers, water heaters and pressure vessels. Two documented changes, new Section 931 on steam bath equipment and a pressure vessel scope exception, plus the installation, relief and clearance rules inspectors check first.
Chapter 12 governs hydronic piping for radiant floors, panel heating, snow and ice melt, and central hydronic distribution. Two documented changes on radiant and snow melt tubing, plus materials, pumps, expansion and commissioning.
The companion to the A2L hour: the four remaining Chapter 11 changes on refrigerant piping locations, surface temperature, pipe identification and hazard labels, shield plates and shaft ventilation, plus leak detection and emergency response.
Every Florida electrical and alarm contractor renews against the same three bodies of law: Chapter 455, Chapter 489 Part II, and F.A.C. Division 61G6. What each one requires of you.
On December 31, 2026 the 2026 Florida Building Code, 9th Edition moves Florida from the 2020 NEC to the 2023 NEC, and wraps it with rules you will not find in NFPA 70: rooftop clearances, HVHZ, flood zones, and hurricane standby power.
The 2023 NEC moved nearly every definition into Article 100, pushed GFCI protection into more rooms and onto more appliances, created the 10 ampere branch circuit, and added surge protection and outdoor emergency disconnects to feeders.
Picks up at Article 240 and runs through the rest of the book: the 5000 A interrupting rating floor, no breakers in any bathroom, the reorganized equipment grounding conductor list, the renumbered burial depth table and the Chapter 7 reorganization.
Article 250 is where inspectors fail more work than anywhere else, and most failures are the same five things: an electrode never bonded in, a water pipe as the only electrode, a short ground rod, an undersized GEC, a missing bond.
Chapter 3 is the part of the NEC you use most and read least. The rules that decide a rough-in: trench depth, which cable goes in which building, PVC expansion fittings, raceway fill, plenums and supports.
Every breaker in a panel is doing one of four jobs: protecting the conductor, protecting a person from shock, protecting equipment from ground fault, or protecting the building from an arcing fault. Which rule covers which.
Power enters a building once, through a service, then fans out through feeders and branch circuits. Articles 230, 215, 225 and 210 govern that path, and the 2023 NEC changed the parts a service contractor touches most.
The 2026 Florida Building Code, Plumbing, 9th Edition takes effect December 31, 2026. It is built on the 2024 IPC, but Florida amends it for termites, high water tables, private wells, reclaimed water and public pools.
Or get the whole thing in one click
Every mandatory hour and every technical hour your board requires, one purchase, one price. A package saves $110 to $137 against buying the same hours one at a time.